Application:
Hvac refrigeration and indoor air quality monitoring. Industrial process and safety monitoring. Agricultural and animal husbandry production process monitoringProduct characteristics:
excellent stability1. Description
TX721-A1 infrared carbon dioxide gas sensor is a general purpose intelligent infrared gas sensor, the sensor uses non-dispersive infrared (NDIR) principle to detect CO2 in the air, the sensor has no oxygen dependence, stable performance and long life. Built-in temperature compensation.
2. Technical specifications
Project | TX721-A1 |
Detected gas | CO2 |
Working voltage | 3.6~5 .0V DC |
Average current | < 85 mA |
Maximum measurement range | 0~10% Vol |
Interface level | 3.0V |
Output signal | UART 0.4~2 .0V |
Preheating time | 3 min |
Response time (T90) | T90<30S |
Temperature range | -20℃~60 ℃ |
Humidity range | 0~95% RH |
Dimension | Φ20×22.4mm |
Weight | 35 g |
Life span | > 5 years |
Levels of protection | IP54 |
Parameters of the power supply terminals and communication terminals | Ui=7.5VDC,Ii=265mA,Pi=0.5W, Ci=10 μF, Li=0mH |
3. Sensor Size
4.Intrinsically safe explosion-proof
This product complies with GB3836.1-2010 "Explosive Atmospheres Part 1: General Requirements for Equipment" and GB3836.4-2010 "Explosive Atmospheres Part 4: Equipment Protected by Intrinsically Safe "i"" standards; the explosion-proof mark is Exib ⅡB T4 Gb, which is suitable for Zone 1 and Zone 2, containing Class IIA, T1~T3 combustible gases, steam and air mixed with explosive environments; it has passed the inspection of the National Explosion-proof Electrical Products Quality Inspection Center and obtained an explosion-proof certificate. When using, please pay attention to the following matters:
The sensor must be powered by an intrinsically safe power supply, otherwise it will affect the explosion-proof performance.
It is prohibited to replace the sensor in a hazardous area.
It is prohibited to disassemble or replace the sensor element to avoid affecting the explosion-proof performance.
It is not allowed to replace components or structures to avoid affecting the explosion-proof performance.
The installation and wiring of the safety barrier must be carried out in accordance with the safety barrier instruction manual, and the safety barrier must obtain an explosion-proof certificate.
5.Notes
The sensor should be calibrated regularly, and the recommended calibration period is 6 months.
Do not use the sensor for a long time in an environment with high dust density.
The sensor should be kept away from heat sources and avoid direct sunlight or other heat radiation.
Please use the sensor within the power supply range of the sensor.
Do not cut or weld the sensor pins.